b'LT ENGINEERINGCATALOGExample: Farm accident: Victim pinned under chemical spreader. On scene, First Responder, Sheriffs Deputy, and two Emergency Medical Technicians giving assistance.All on site have been exposed to chemicals. All involvedat incident will be decontaminated at Hospital X.Hospital X has a decontamination room equipped witha single stand up shower and one drench hose that deliver 5.5 GPM. The decontamination room is served by one drain.The calculation is as follows:4 Stand up showers x 5.5 gpm head x 15 minutes= 330.0 gallons1 Drench shower x 5.5 gpm head x 15 minutes = 82.5 gallonsMinimum DeconTank Size = 415.5 gallonsThe same calculations using a 20 gallon per minutedeluge shower would require a minimum of a 1,500m gallon containment tank(s). Current sizes available are shown below.Decontamination Tank Model SizesMODEL GAL DIA D FL WT LBSDTC-500 500 60" 54" 42" 10,100DTC-600 600 60" 60" 48" 10,800DTC-700 700 60" 66" 54" 11,400DTC-800 800 72" 58" 46" 13,200DTC-900 900 72" 64" 52" 14,000DTC-1000 1,000 72" 68" 56" 14,500DTC-1200 1,200 84" 62" 50" 18,000DTC-1500 1,500 96" 60" 48" 19,600DTC-2000 2,000 96" 74" 62" 21,900DTC-2500 2,500 96" 88" 76" 24,200396 INFO@PARKUSA.COM|888-611-7275|WWW.PARKUSA.COM'