b'How it WorksAs precipitation falls on a heliport landing pad, the resulting stormwater runoff drains away from the pad via a plumbing drainage system. The drainage system often drains through a building on its way to a stormwater or sanitary sewer.In the event of a helicopter crash or accidental fuel spill, the runoff could contain dangerous components that put the building and public sewer at risk for re and explosion.The function of a fuel-water separator is to intercept fuel and oils from the heliport drainage system and then safely detain it for removal. Runoff ows from the landing pad into the drainage system and then to the HeliCepter heliport separator.The runoff enters the separators inlet chamber where any present fuel slugs rise immediately to the surface. The remaining fuel-laden wastewater ows through the patented coalescing media where remaining hydrocarbon droplets and ne solids are progressively separated. All the separated hydrocarbons rise to the upper area of the separator and are securely detained. Downstream, the patented fuel-stop valve prevents the release of harmful fuels from exiting the separator. Hazardous fumes are vented from the separator and safely away from the building and the public sewer.System Components Options Maintenance is made easy by the The HeliCepter fuel-water separators Elevated stands & ladders automatic monitoring system that have the following components, Dual wall construction noties the operator of hydrocarbon making it superior to all other Insulated tanks and electrichigh levels. Once activated, the operator separators on the market: heaters has the separator cleaned by a qualiedUL 2085 fuel storage tank service company. An auxiliary storagePatented coalescing media Precast concrete vault tank can be utilized to increase the technology enclosure storage capability Patented fuel-stop valve of the separator system. Stainless steel construction Easy access cover withVisit helicepter.parkusa.com for more fall-protection information and design assistance. Automatic service/alarm report system To request a quote or catalog, visit15 year warranty request.parkusa.com.APPLICATIONSGeneral Medical Offshore/ Commercial Municipal MunicipalAviation Facilities Marine Airports'