b'LT ENGINEERINGCATALOGSEPARATOR DATAFLOW CAPTOTALOIL SPILLDIA D HEIGHT H INLET FL1 OUTLET FL2GPM CAPACITY CAPACITY50 60 GAL X GAL 8 51 43 9SEPARATOR DATAFLOW CAPTDH DISH SIZE RPM HP VOLT / PH PUMPGPM50 15 1 1/2 3450 .50 120 / 1 LIBERTY 280Example:A common application would be a building with four (4) elevator shafts with containment sumps discharging 50 gpmWastewater Systemseach. The Elevator Oil-Water Separator requirement would be 200 gpm. MAINTENANCEOne of the most important features for the successful1.Remove cover.operation of the Elevator Oil-Water Interceptor is the2. Drain the water from the vessel.maintenance program. Regardless of the size or design,3. The plate packs may either be cleaned in place or an interceptor is only as good as its maintenance program.removed and cleaned. To clean the packs, first stop the For this reason, most plumbing codes require theflow to the unit, remove the oil, and drain the water.interceptor to be installed and located so that it will be easily accessible for inspection, cleaning, and removal of4. For cleaning in place, connect a pressure water hoseintercepted hydrocarbons. (at least 60 psi) to the special plate cleaning wand (available as an option). Provide a vacuum truck or other The frequency of cleaning at any given installation will varymeans of disposing of the sludge and dirt in the vessel. depending on use. The Elevator Oil-Water Separator shouldTurn on the water to produce a spray from the wand and be inspected at least biannually. The High Oil Alarm systeminsert slowly into each hole of the plate pack, starting will warn facility of any immediate servicing requirements.at the upstream end. As the water flushes the dirt out When necessary, the separator should be pumped out byof the plate packs into the inlet chamber, it should be a licensed pumping company familiar with regulationsremoved by the vacuum hose or to an oily water sewer.regarding proper disposal.After approximately 30 days of operation, the inlet area of the separator should be checked to determine if an excessive amount of oils and solids have accumulated. After approximately the first 1000 hours of operation,the inlet area should be cleaned as follows:INFO@PARKUSA.COM|888-611-7275|WWW.PARKUSA.COM 329'