b'STORMWATERCATALOGSEQUENCE OF OPERATION-600 Gal. Acid TankNormal ConditionWhen the system is operating within normal conditions, the pH levels are within 5-9 pH and the leak detectionsensor in in the open condition.All indicators are de-energized.Rotating the "TEST" switch (g) to the left(counter-clockwise) will momentarily test all alarm relays, indicator lights and the audible alarm.The touchscreen readout (p) indicated all items are operating within normal parameters.High pH Level Alarm ConditionWhen the pH of the wastewater rises above the set limit (9 pH), the "HIGH pH" indication light (b) and theaudible alarm (h) are energized.Rotating the "SILENCE" switch (f) to the right (clockwise) de-energizes theaudible alarm (h).The touch screen readout (p) will indicate pH reading on line (r).After alarm condition iscleared (pH level returns to normal operating conditions), the monitoring panel will automatically reset tonormal condition.Low pH Level Alarm ConditionWhen the pH of the wastewater drops below the set limit (5 pH), the "LOW pH" indication light (b) and theaudible alarm (h) are energized.Rotating the "SILENCE" switch (f) to the right (clockwise) de-energizes theaudible alarm (h).The touch screen readout (p) will indicate pH reading on line (r).After alarm condition iscleared (pH level returns to normal operating conditions), the monitoring panel will automatically reset tonormal condition.Data LoggingTrending data is retrieved by 4 methods.The first method is by visually inspecting the touch screen (p).This method gives the user access to themost current trending data samples.History can be viewed as a line graph or raw data.The second method is to download the logged data to a USB thumb drive through the front USB port (x) onthe controller (w).Logged data is available in *.csv (comma delimited) format for use in a spreadsheet.The third method is remote network access.If network access has been set up the user can access currenttrending data across a local network (internet access to be granted through a VPN on the user\'s localnetwork).Logged data can be retrieved via a downloadable *.csv file.The fourth method of data retrieval is via emailed reports.Reports of logged data can be setup to be emailon programed regular intervals.Logged data is emailed in *.csv format.270 INFO@PARKUSA.COM|888-611-7275|WWW.PARKUSA.COM'