b'STORMWATERCATALOGSEQUENCE OF OPERATION-100 Gal. Acid TankNormal ConditionWhen the system is operating within normal conditions, the pH levels are within 5-9 pH and the leak detection sensor in in theopen condition. All indicators are de-energized.Depressing any of the push to test LED switches (b,c,e) will momentarily test thealarm relay, indicator lights and the audible alarm.The touch screen readout (p) indicated all items are operating within normalparameters.High pH Level Alarm ConditionWhen the pH of the wastewater rises above the set limit (9 pH), the "HIGH pH" indication light (b) and the audible alarm (h) areenergized.Depressing the "SILENCE" switch (f) de-energizes the audible alarm (h).The touch screen readout (p) will indicate pHreading on line.After alarm condition is cleared (pH level returns to normal operating conditions), the monitoring panel willautomatically reset to normal condition.Low pH Level Alarm ConditionWhen the pH of the wastewater drops below the set limit (5 pH), the "LOW pH" indication light (c) and the audible alarm (h) areenergized.Depressing the "SILENCE" switch (f) de-energizes the audible alarm (h).The touch screen readout (p) will indicate pHreading on lineAfter alarm condition is cleared (pH level returns to normal operating conditions), the monitoring panel willautomatically reset to normal condition.Leak Detection ConditionWhen the leak detection sensor detected a water level in the containment vault.As the water level reaches a depth about 1-2",the leak detection sensor (k) float rises.The red "LEAK DETECTION" indication light (e) and the audible alarm (h) are energized.Depressing the "SILENCE" switch (f) de-energizes the audible alarm (h).The touch screen readout (p) will indicate to "INSPECTVAULT on line (t).After alarm condition is cleared (liquid evacuated from the containment vault), the monitoring panel willautomatically reset to normal condition.268 INFO@PARKUSA.COM|888-611-7275|WWW.PARKUSA.COM'